S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA INSTALLATION / OWNER’S MANUAL Improper installation, adjustment, alteration, service or m
10 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA WARNING Improper installation, adjustment, alteration, service or maintenance can ca
11 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 6. MOUNTING CLEARANCES This heater must be mounted with at least the minimum clearances
12 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA * RECOMMENDED MOUNTING HEIGHTS are typical to provide optimum comfort in general space h
13 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA FIGURE 3 SYSTEM ELBOW KIT - see page 50 for 180° elbow dimensions 90° elbows (JS-0528-
14 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 8. SUSPENDING THE SYSTEM - GENERAL Inadequate or improper suspension of the tube heater
15 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 9.1 S100 / ITB STRAIGHT TUBE SYSTEM ~ BURNER AND TUBE INSTALLATION For “U-Tube” Systems
16 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA FIGURE 7 STRAIGHT TUBE TYPICAL HANGER & SUPPORT SPACINGS 6 - ALUMINIZED TUBE WITH
17 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 9.2 S100U / ITBU ‘U’-TUBE SYSTEM ~ BURNER AND TUBE INSTALLATION For “Straight-Tube” Sys
18 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 1) Install Hangers using chain or other suitable suspension hardware at each side of the
19 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA FIGURE 11 ‘U’-TUBE TYPICAL HANGER & SUPPORT SPACING 8 - STEEL TUBE(S) 9 - REFLEC
2 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA NOTICE: This manual is current for this product. Occasional revision of the product Cert
20 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA SPECIAL COUPLER INSTALLATION 1. Install first tube so that the welded seam along the tu
21 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA SPECIAL COUPLER INSTALLATION 1. Note the 2 holes opposite each other at the swaged end
22 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 9.4 STRAIGHT TUBE SEISMIC RESTRAINT - LATERAL AND LONGITUDINAL In areas prone to earth
23 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 9.6 ‘U’ TUBE SEISMIC RESTRAINT In areas prone to earthquake, or as specified on a pro
24 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 10. REFLECTOR INSTALLATION S100-U / ITB-U - U’-TUBE: After burner and tubes have been i
25 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA FIGURE 19 REFLECTOR EXTENSIONS (OPTIONAL - IF REQUIRED ) 1. Reflector extension
26 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 12. FLUE VENTING Inadequate venting of a heater may result in asphyxiation, carbon mo
27 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA HORIZONTAL VENT THROUGH THE SIDEWALL: Any horizontal portion of the flue vent system
28 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA Use approved 4" (10 cm) (JA-0528-XX) or 6" (15 cm) (JA-0529-XX) horizontal
29 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA VERTICAL VENT THROUGH THE ROOF: It is the sole responsibility of the installer to adhere
3 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA TABLE OF CONTENTS TOPIC ...PAGE INSTAL
30 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 13. COMBUSTION AIR DUCTING Do not install filters on the combustion air intake. Ensure
31 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 13. GAS SUPPLY - HEATER EXPANSION - FLEXIBLE GAS CONNECTION The gas supply must be insta
32 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA NOTE: Access to the manifold pressure test port is on the top of the valve. A 3/16"
33 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA The flue vent, and combustion air duct (if installed) must also be configured in such a
34 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 14. ELECTRICAL AND THERMOSTAT WIRING (WIRING DIAGRAMS PAGE 35 & 36) The heater
35 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 18A. WIRING DIAGRAM: 120 VOLT THERMOSTAT OPERATION (24V Thermostat—next page) Maximum
36 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 18B. WIRING DIAGRAM: 24 VOLT THERMOSTAT OPERATION (120V Thermostat - previous page) Ma
37 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 19. MULTIPLE TUBE HEATERS per THERMOSTAT Each tube heater requires 120V, 60 HZ electr
38 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 20 SEQUENCE OF OPERATION The S87 ignition control module is powered by a 24v transforme
39 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA CHECK 120V SUPPLY TO RELAY SWITCH IF ELECTRICAL SUPPLY PROBLEM …. MAKE RE-QUIRED R
4 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA APPLICATION A gas-fired radiant tube heater may be installed for heating of commercial /
40 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA MAIN BURNER LIGHTS SYSTEM RUNS UNTIL CALL FOR HEAT ENDS CALL FOR HEAT ENDS: SYSTEM SHUT
41 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 22. SPARK IGNITION CIRCUIT The step-up transformer in the ignition control provides sp
42 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA LOW/ UNSTEADY FLAME CURRENT If the current to the S87 flame circuit is less than 1.5 µA
43 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 24. START-UP / COMMISSIONING SHEET COMMISSIONING
44 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA TYPE OF GAS: NG LP DOES BUILDING HAVE A NEGATIVE CONDITION: YES NOIF THIS IS A HIGH
45 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 25A. BURNER & TUBE KIT ASSEMBLY CHART MODELS S100 / ITB MODELS S100 & ITB are
46 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 25B. BURNER & TUBE KIT ASSEMBLY CHART MODELS S100U / ITBU MODELS S100U & ITBU
47 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 26. MODEL INPUT RATINGS (BTUH ) AND DIMENSIONS BTUH INPUT 0’ to 4500’ ABOVE S
48 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA Tube Length ‘L’ = center air intake to end 10’ 11’-3 3/4” ; 135 3/4” ; 345 c
49 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA S100 / ITB 110-50 not required S100 / ITB 130-30 14' (4.3 m) S100 / ITB 130-40
5 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA Heater Expansion It is a normal condition that during heat-up and cool-down a tube heate
50 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA When this appliance is installed above the altitude stipulated below, the input must be
51 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA ORIFICE CHART - ALTITUDE CONVERSION ~ SEE NOTES ON PREVIOUS PAGE ~ 28. HIGH ALTITUDE
52 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 29. OPTIONAL ACCESSORIES #2 Lion Chain (115 lb work load) - 200 ft roll ‘S’ Hooks - 1
53 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA Fresh Air Intake Adapter JS-0532-SE Fresh Air Intake Cap—Wall JS-0532-VC Fresh Air Intak
54 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA Low Voltage Digital Thermostat (24 Volts - °F or °C selectable) Not for use in corrosiv
55 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 90 degree Aluminized Steel Elbow Kit (Kit includes: aluminized steel elbow, coupler, an
56 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA Optional Items 22 730 REPLACEMENT PARTS S100 / ITB Burner # PART DESCRIPTION PART #
57 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA # PART DESCRIPTION PART # PART DESCRIPTION PRIMARY SUPPLEMENT 6 BURNER CHAMBER JS-0504-
58 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA S100 / ITB & S100U / ITBU TUBE SYSTEM PARTS # PART DESCRIPTION PART # PART DESCRI
59 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA LIMITED WARRANTY CERTIFICATE FOR GAS-FIRED INFRA-RED LOW INTENSITY TUBE HEATERS: S100 /
6 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA Clearance to combustibles Location of flammable or explosive objects, liquids or vapors
7 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES
8 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA VENT END CLEARANCE: Clearances from the vent pipe are determined by local or national ins
9 S100/ITB I&O Manual IM101230 RD: SEP 2013 RL: 8B- BA 2. INSTALLATION IN COMMERCIAL AIRCRAFT HANGARS Low intensity radiant tube heaters are su